LZAB1-C40 miniature circuit breaker
Applicable Scope
The LZAB1 series miniature circuit breaker (hereinafter referred to as the circuit breaker) is a type of limited current high breaking miniature circuit breaker with dual protection against overload and short circuit. It is suitable for circuits with rated working voltage of 230V/400V at 50Hz/60Hz and rated current up to 125A and below, and is used for overload and short circuit protection of lines, lighting, and power equipment. It can also be used for infrequent switching of lines and equipment under normal circumstances. It has the characteristics of beautiful and compact appearance, light weight, easy installation, excellent and reliable performance. The product complies with GB/T10963.1 and IEC60898-1 standards.
Working Conditions
1. The upper limit of the surrounding air temperature shall not exceed+40 ℃, the lower limit shall not be lower than -5 ℃, and the average temperature value over 24 hours shall not exceed+35 ℃; Note 1: For working conditions with a lower limit of -10 ℃ or -25 ℃, users must declare it to the manufacturer when placing an order; Note 2: For working conditions where the upper limit exceeds+40 ℃ or the lower limit is below -25 ℃, the user should consult with the manufacturer.
2. The altitude of the installation site shall not exceed 2000m;
3. The relative humidity of the atmosphere should not exceed 50% when the ambient air temperature is+40 ℃. Higher relative humidity is allowed at lower temperatures, such as reaching 90% at+20 ℃. Appropriate measures should be taken for occasional condensation caused by temperature changes;
4. Pollution level: Level 2;
5. Installation category: Class II and Class III;
6.The external magnetic field of the installation site should not exceed 5 times the geomagnetic field in any direction;
7. Generally installed vertically, with a tolerance of 2 ° in any direction;
8. The installation site should have no significant impact or vibration.
Structure Characteristics
Main Technical Indicators
|
Model |
Number of poles |
Rated voltage Ue(V) |
Rated current In(A) |
Rated ultimate short-circuit breaking capacity Icu (A) |
Instantaneous release type and tripping current multiple |
|
LZAB1-63 |
1、2 3、4
|
230/400
|
1、3、6、10、16 20、25、32、40 50、63
|
4000 |
Type B - (3-5) In Type C - (5-10) ln Type D - (10-20) In
|
|
LZAB1-63H |
6000 |
||||
|
LZAB1-125 |
1、2 3、4 |
230/400 |
63、80、100 |
10000 |
Type C - (5-10) ln Type D - (10-20) In |
2. Overcurrent protection characteristics
|
Serial number |
Rated current In |
Starting State |
Test current |
Schedule |
Expected Results |
Remark |
|
a
|
In≤63A |
Cold
|
1.13In
|
t≥1h |
No tripping
|
|
|
In>63A |
t≥2h |
|||||
|
b
|
In≤63A |
Immediately after test A
|
1.45In
|
t<1h |
Tripping
|
The current rises steadily to the specified value within 5s
|
|
In>63A |
t<2h |
|||||
|
C
|
In≤32A |
Cold
|
2.55ln
|
1s<t<60s |
ripping
|
|
|
In>32A |
1s<t<120s |
|||||
|
d
|
All values
|
Cold
|
3In |
t≤0.1s
|
No
|
Type B |
|
5In |
Type C |
|||||
|
10ln |
Type D | |||||
|
e
|
All values
|
Cold
|
5In |
t<0.1s
|
Tripping
|
Type B |
|
10ln |
Type C |
|||||
|
20ln |
Type D |
Installation Dimensions